6.4.9 Auxiliary DC power outputs
The MV UPS provides 24 Vdc auxiliary power supply for the Energy Storage, Generators, and external Demand Re-
sponse Controllers.
Table 6.03 shows the terminals' configuration. The current on each output must not exceed 10 A.
Terminal
Number
X6
1
X6
2
X7
1
X7
2
X8
1
X8
2
X23
1
X23
2
Table 6.03: Auxiliary DC
power connections.
Description
Energy Storage Interface +24 Vdc
Energy Storage Interface 0 Vdc
Switchgear Interface +24 Vdc
Switchgear Interface 0 Vdc
Demand Response Controller Interface +24 Vdc
Demand Response Controller Interface 0 Vdc
Generator Interface +24 Vdc
Generator Interface 0 Vdc