NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2.
Cut JP30 on the MS-5UD/MS-10UD main circuit board to supervise placement of SK-4XTMF
module and circuit.
3.
Cut JP24 on the MS-5UD/MS-10UD main circuit board to enable FACP Supervisory relay.
4.
Refer to "4XTMF Transmitter Module Installation" on page 39 for detailed information.
Polarities shown in alarm condition
Figure B.2 Municipal Box Connected to 4XTMF Transmitter Module
148
Municipal Box Circuit
Nonpower-limited
-
+
4XTMF
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
FIRE
+
-
Gamewell Model M34-56
Local Energy Municipal
Box