Programming
Pressing the down arrow key will display additional zone types as indicated in the following table.
Some of the following Zone Types are not available for Canadian applications. Refer to "Canadian
Option" on page 81 for additional details.
Zone Type
Pull-Station
Waterflow
Waterflow Nonsilenceable
Combo
Combo AutoResettable
2-Wire Detector
Normally Open Contact
Fire
Tamper
Supervisory
Supervisory AutoResettable
Medic-Alert
Hazard-Alert
Tornado-Alert
Proc-Mon
Procmon-AR
AC-Loss-Mon
Ack-Switch
Sil-Switch
Drill-Switch
Reset-Switch
PAS-Bypass
Drill-Switch AutoResettable
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
NOTE:
assigned message with the exception of ACKNOWLEDGE, SILENCE, RESET and PAS
BYPASS Switches. The DRILL Switch (or input programmed as a drill switch) will cause all of
the corresponding ACC-25/50ZST audio zones to go active and will output Message 1.
64
Almost any Input Zone type can activate an ACC-25/50ZST audio zone and output an
Action When Activated
Fire Alarm
Fire Alarm Delayed (uses waterflow delay)
Fire Alarm (uses waterflow delay)
Fire/Supervisory (uses waterflow delay)
Fire/Supervisory AR, nonlatching (uses waterflow delay)
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory
Supervisory, latching
Supervisory, nonlatching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Piezo
Piezo, nonlatching
Trouble
Acts like panel Acknowledge Key
Acts like panel Alarm Silence Key
Acts like panel Drill Key
Acts like panel Reset Key
Positive Alarm Sequence Disable
Acts like panel Drill Key, nonlatching
Table 3.1 Zone Types
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Master Programming Level