Appendix B: NFPA Standard-Specific Requirements

The MS-5UD/MS-10UD has been designed for use in commercial, industrial and institutional
applications and meets the requirements for service under the National Fire Protection Association
(NFPA) Standards outlined in this Appendix. The minimum system components required for
compliance with the appropriate NFPA standard are listed below:
MS-5UD/MS-10UD Control Panel
Contains the main control board, cabinet (backbox and door), main power supply and transformer.
Batteries
Refer to "Power Supply Calculations" on page 135, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
The following additional equipment is needed for compliance with the NFPA 72 standards listed
below:
NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service
NFPA 72 Auxiliary Fire Alarm System
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled "4XTMF Transmitter Module Installa-
tion" on page 39 and as outlined in Figure B.2, "Municipal Box Connected to 4XTMF Transmitter
Module," on page 148.
NFPA 72 Proprietary Fire Alarm System
MS-5UD/MS-10UD Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See
Figure B.4, "Proprietary Protective Signaling System," on page 150, for installation instructions for
this unit.
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed
Central Station DACR or Protected Premises Receiving Unit. This unit must be installed
as outlined in "Digital Alarm Communicator/Transmitter" on page 21.
OR
411UD may be installed as illustrated in Figure B.1, "MS-5UD/MS-10UD FACP
Connection to 411UD," on page 146.
OR
4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver. See
Figure B.3, "Remote Station Connection Using 4XTMF Module," on page 149, for
installation instructions for this unit.