Honeywell Fire-Lite Alarms MS-5UD Series Manual page 143

Fire alarm control panels
Table of Contents

Advertisement

Ademco Contact ID Typical Printout
EVENT
System Peripheral Troubles - 330 and 340
330 System peripheral
331 Polling loop open
332 Polling loop short
333 Expansion module failure
334 Repeater failure
335 Local printer paper out
336 Local printer failure
Communication Troubles - 350 and 360
350 Communication
351 Telco 1 fault
352 Telco 2 fault
353 Long range radio xmitter fault
354 Fail to communicate
355 Loss of radio supervision
356 Loss of central polling
Protection Loop Troubles - 370
370 Protection loop
371 Protection loop open
372 Protection loop short
373 Fire trouble
Sensor Troubles - 380
380 Sensor trouble
381 Loss of supervision - RF
382 Loss of supervision - RPM
383 Sensor tamper
384 RF transmitter low battery
Open/Close - 400
400 Open/Close
401 Open/Close by user
402 Group Open/Close
403 Automatic Open/Close
404 Late Open/Close
405 Deferred Open/Close
406 Cancel
407 Remote arm/disarm
408 Quick arm
409 Keyswitch Open/Close
Remote Access - 410
411 Callback request made
412 Success - download/access
413 Unsuccessful access
414 System shutdown
415 Dialer shutdown
416 Success - upload/access
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Ademco Contact ID Format Event Code Descriptions
MESSAGE
TROUBLE - Sys. Peripheral - #
TROUBLE - Polling Loop Open
TROUBLE - Polling Loop Short
TROUBLE - Exp. Module Fail - #
TROUBLE - Repeater Failure - #
TROUBLE - Printer Paper Out
TROUBLE - Local Printer
TROUBLE - Communication Trouble
TROUBLE - Phone Line #1
TROUBLE - Phone Line #2
TROUBLE - Radio Transmitter
TROUBLE - Fail to Communicate
TROUBLE - Radio Supervision
TROUBLE - Central Radio Polling
TROUBLE - Protection Loop - #
TROUBLE - Protection Loop Open - #
TROUBLE - Protection Loop Short - #
TROUBLE - Fire Loop - #
TROUBLE - Sensor Trouble - #
TROUBLE - RF Sensor Supervision - #
TROUBLE - RPM Sensor Supervision - #
TROUBLE- Sensor Tamper - #
TROUBLE - RF Sensor Batt. - #
OPENING
OPENING - User #
OPENING - Group User #
OPENING - Automatic
OPENING - Late
Opening not used
OPENING - Cancel
OPENING - Remote
Opening not applicable
OPENING - Keyswitch
REMOTE - Callback Requested
REMOTE - Successful Access
REMOTE - Unsuccessful Access
REMOTE - System Shutdown
REMOTE - Dialer Shutdown
REMOTE - Successful Access
CLOSING
CLOSING - User #
CLOSING - Group User #
CLOSING - Automatic
CLOSING - Late
Closing not used
Closing not used
CLOSING - Remote
CLOSING - Quick Arm
CLOSING - Keyswitch
(restore not applicable)
(restore not applicable)
(restore not applicable)
(restore not applicable)
143