ANN-BUS Devices

Mounting

The ANN-80 can be surface or semi-flush mounted to a single, double or 4" square electrical box.
Select and remove the appropriate knockout(s), pull the necessary wires through the knockouts and
mount the annunciator in or on the wall depending on the type of installation desired.
The ANN-SB80KIT(-R/-B/-W) is an available mounting kit for the ANN-80 annunciator. The kit
comes with a surface backbox and surface wedge for angled viewing. The two pieces can be used
separately or can be stacked together.
The ANN-80 cover must be attached to the annunciator backplate before mounting the annunciator
to the electrical box/wall. The cover cannot be reattached or removed after the annunciator has
been mounted.
Annunciator mounted on
surface wedge from the
ANN-SB80KIT

Wiring ANN-80 to FACP

The following steps can be used as a guide to wire the annunciator. Make certain all power has
been removed from the FACP prior to annunciator installation.
1.
Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal
block TB1.
TB1
2.
Remove appropriate amount of wire insulation.
3.
Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B.
4.
If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals
3 & 4. Make certain to connect A to A and B to B.
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Annunciator mounted on
surface backbox from the
ANN-SB80KIT
wiring channel
wires
Installation
Annunciator mounted on
stacked surface wedge
and backbox from the
ANN-SB80KIT