Programming
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the display
will return to NAC Screen #1.

Silence Inhibited

The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board
NAC for a period of one minute. Resetting the FACP will also be prevented for one minute while
the NAC programmed for silence inhibit is activated. Pressing 3 while viewing NAC Screen #2
will cause a screen to be displayed with the options 1=No Silence Inhibit and 2=1 Min. Silence
Inhibit. Pressing 1 will disable the Silence Inhibit feature while pressing 2 will enable a 1 minute
Silence Inhibit for the selected Output.
3.5.3 Relays
PROGRAMMING
Pressing 3 while viewing Programming Screen #1 will allow the programmer to configure the three
1=INPUT ZONES
main circuit board Form-C relays. The following screen will be displayed:
2=NACS

3=RELAYS

Programming Screen #1
To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following
screens will appear for each relay to be programmed:
RELAY TYPE
1=ALARM
2=TROUBLE
3=SUPERVISORY
Relay Screen #1
RELAY TYPE
1=COMM FAIL
2=MEDICAL
3=SILENCEABLE ALARM
Relay Screen #3
74
RELAYS
1=RELAY 1
ALARM
2=RELAY 2
TROUBLE
3=RELAY 3
SUPERV
Relays Selection Screen
1=PROCESS MONITOR
2=AC LOSS
3=HAZARD
Relay Screen #2
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Master Programming Level
RELAY TYPE