Process Monitor Operation; Hazard/Tornado Condition Operation; Medical Alert Condition Operation - Honeywell NOTIFIER NFW-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for NOTIFIER NFW-50X:
Table of Contents

Advertisement

Operating Instructions
A typical Supervisory event would be displayed as illustrated in the following:
Note that, like alarms, supervisory signals latch (except when programmed for supervisory autoresettable) and can be assigned to soft-
ware zones. Supervisory alarms do not cause resound as do other alarm conditions. Open circuits in supervisory wiring are processed by
the control panel the same way as other trouble conditions. Refer to "Alarm Operation" on page 104, for a description of the information
displayed on the control panel LCD.

4.8 Process Monitor Operation

Process Monitor operation will initiate the following events:
The piezo sounder pulses ¼ second On and ¼ second Off
The LCD displays a process monitor message along with the device name, type, address, adjective/noun, associated zones, and
time/date
Communicate the process monitor condition to the Central Station (if the default event code has been changed from 000 to a
reportable event code)
Relays programmed for process monitoring will be activated
The alarm relay is not activated
Fire Alarm NACs will not activate
SLC NACs (control modules) will activate
Timers are not started
Store event in history buffer
Activate appropriate LED on the N-ANN-LED annunciator (required for this application)
Each N-ANN-LED can support up to 10 zones.
Note that, like supervisories, process monitor signals latch (except when programmed for process monitor autoresettable) and can be
assigned to software zones.

4.9 Hazard/Tornado Condition Operation

Hazard/Tornado operation is intended for Manual activation.
Hazard/Tornado Condition operation will initiate the following events:
The piezo sounder pulses 1/4 second On, 1/4 second Off
The LCD displays a hazard message along with the device name, type, address, adjective/noun, associated zones, and time/date
Communicate the hazard condition to the Central Station (if the default event code has been changed from 000 to a reportable event
code)
Relays programmed for hazard will be activated
The alarm relay is not activated
Fire Alarm NACs will not activate
SLC NACs (control modules) will activate
Timers are not started
Store event in history buffer
Activate appropriate LED on the N-ANN-LED annunciator (required for this application)
Each N-ANN-LED can support up to 10 zones.
Hazard conditions latch. They can be assigned to software zones.

4.10 Medical Alert Condition Operation

Medical alert operation is:
not intended for nurse call stations (applications) per UL1069.
not intended for signaling professional medical staff.
to be used for summoning security guards or other trained personnel within the facility
intended for Manual activation.
Medical Alert Condition operation will initiate the following events:
The piezo sounder 1/4 second On, 1/4 second Off
The LCD displays a medical alert message along with the device name, type, address, adjective/noun, associated zones, and
time/date
Communicate the medical alert condition to the Central Station
Relays programmed for medical alert will be activated
The alarm relay is not activated
Fire Alarm NACs will not activate
SLC NACs (control modules) will activate
106
ACTIVE SUPERVISORY
<ADJ> <NOUN>
Z000
10:00A 012116 1M001
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Process Monitor Operation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents