5.2 Installation location

Make sure that the installation location meets the following conditions:
1) The area is completely waterproof.
2) The floor is flat and level.
3) There are no flammable or explosive materials.
4) The ambient temperature is within the range from 0°C to 50°C.
5) The temperature and humidity are maintained at a constant level.
6) There is minimal dust and dirt in the area.
7) The distance from heat source is more than 2 meters.
8) The distance from air outlet of inverter is more than 0.5 meters.
9) The installation areas shall avoid of direct sunlight.
10) The Minimum clearance to battery module(rack) is more than 0.5 mm.
11) There is no mandatory ventilation requirements for battery module, but
please avoid of installation in confined area. The aeration shall avoid of
high salinity, humidity or temperature.
Caution
If the ambient temperature is out of the operating range, the battery stops
operating to protect itself. The optimal temperature range for the battery pack
to operate is 10°C to 40°C. Frequent exposure to harsh temperatures may
deteriorate the performance and life of the battery.