4.2 Installation location

Make sure that the installation location meets the following conditions:
1)
The area is completely water proof
2)
The floor is flat and level.
3)
There are no flammable or explosive materials.
4)
The ambient temperature is within the range from 0°C to 50°C.
5)
The temperature and humidity is maintained at a constant level.
6)
There is minimal dust and dirt in the area.
7)
The distance from heat source is more than 2 meters.
8)
The distance from air outlet of inverter is more than 0.5 meters.
9)
The installation areas shall avoid of direct sunlight.
10) There is no mandatory ventilation requirements for battery module, but
please avoid of installation in confined area. The aeration shall avoid of
high salinity, humidity or temperature.