Overview Of Diagnostic Events; Behavior Of The Device In The Event Of A - Endress+Hauser Liquiphant FTL33 IO-Link Operating Instructions Manual

Point level switch for liquids in the food sector
Hide thumbs Also See for Liquiphant FTL33 IO-Link:
Table of Contents

Advertisement

Liquiphant FTL33 IO-Link
12.4

Overview of diagnostic events

Status
Diagnostic
signal/
behavior
Diagnostic
event
F270
IO-Link error
S804
IO-Link warning
C485
IO-Link warning
C182
IO-Link message
C103
IO-Link message
IO-Link message
IO-Link
information
S825
IO-Link warning
F042
IO-Link error
12.5
Behavior of the device in the event of a fault
The device displays warnings and faults via IO-Link. All the device warnings and faults are for
information purposes only and do not have a safety function. The errors diagnosed by the
device are displayed via IO-Link in accordance with NE107. In accordance with the diagnostic
Endress+Hauser
EventCode
Event text
0x5000
Defect in electronics/
sensor
0x1801
Load current > I
output
Switch output
defective
0x8C01
During simulation of
the switch output or
current output, the
device issues a
warning message for
the duration of the
simulation.
0x1807
delta[%] too small
during calibration
0x1813
Sensor check failed
0x1814
0x1815
0x1812
Ambient temperature
outside of specification
0x1816
Diagnostics and troubleshooting
Cause
Defect in
electronics/sensor
per
Overload at switch
max
output 2
Simulation active
Invalid calibration
Sensor check
failed
Sensor check
passed
Timeout
Reedcontact
Ambient
temperature
outside of
specification
Sensor corroded
Corrective measure
Replace device
• Increase load
resistance at switch
output
• Check output circuit
• Replace device
Switch off simulation
• Verify probe
coverage
• Carry out the
adjustment again
• Clean again
• Replace device
Remove test magnet
Operate measuring
device in specified
temperature range
Replace device
37