4 Installation and Wiring
Signal
cables
(group A)
Signal cables
Power supply cables
Partitioning Methods for Signal and Power Supply Cables
• To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
Power supply
Power supply
Power supply
Parallel Wiring (Single Phase)
• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
• Noise induction may occur if the Controller is installed in a panel that includes high-voltage devi-
ces. Wire and install them as far apart as possible. (Refer to Controller Installation Location on
page 4-38.)
• Either install the Controller a minimum of 200 mm away from high-voltage lines or power lines, or
place the high-voltage lines or power lines in metal tubing and completely ground the metal tub-
ing to 100 Ω or less.
4-42
Signal
Signal
cables
cables
(group B)
(group C)
Signal cables
(a)
(c)
NG
Conduits
Incorrect
Conduits
OK
Correct
Conduits
OK
Correct
Partition
Power
supply
cables
(b)
Signal cables
Power supply cables
(d)
Load
Load
Load
NX-series CPU Unit Hardware User's Manual (W535)