Humidity - Omron NX Series Hardware User Manual

Machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

5 Installation and Wiring
l Forced Ventilation (by Fan at Top of Panel)
Fan
Air filter
Forced Ventilation Method
l Forced Air Circulation (by Fan in Closed Panel)
Fan
Controller
Controller
Forced Air Circulation
l Room Cooling (Cooling the Entire Room Where the Control Panel Is Lo-
cated)
Low Temperatures
The Controller may not start normally if the temperature is below 0°C when the power is turned ON.
Maintain an air temperature of at least approximately 5°C inside the panel, by implementing measures
such as installing a low-capacity space heater in the panel.
Alternatively, leave the Controller power ON to keep the Controller warm.
5-5-2

Humidity

Rapid temperature changes can cause condensation to occur, resulting in malfunctioning due to short-
circuiting.
When there is a possibility of this occurring, take measures against condensation, such as leaving the
Controller power ON at night or installing a heater in the control panel to keep it warmer.
5-58
Controller
Controller
Cooler
Control panel
Room Cooling
NX-series NX502 CPU Unit Hardware User's Manual (W629)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx502-1 00 series

Table of Contents