Address space
The following figure shows the mapping of the address space of the DI 16x24VDC HA.
Table A-2

Address space of the DI 16x24VDC HA

IB x +
7
0
DI7
1
DI15
2
QDI7
3
QDI15
Evaluate value status
There is a bit value status for each digital input in the input address space.
Irrespective of the diagnostics enables, each value status (each QI bit) provides information on
the validity of the corresponding process value.
• Value status = 1: Process value okay, "good"
• Value status = 0: Process value not okay, "bad"
Basically, the value status is set to "good" if the digital value can be detected without error. The
value status is set to "bad" in the following cases:
• The digital value cannot be output due to an error.
• The digital channel is deactivated.
Note
The value status is not set to "bad" when there is a wire break on the channel and the wire break
test is disabled.
A.7

Address space of the time stamping (accuracy 1 ms)

Address space
The following table shows the mapping of the address space of the DI 16x24VDC HA with time
stamping (accuracy 1 ms).
Table A-3

Address space of the DI 16x24VDC HA with time stamping (accuracy 1 ms)

IB x +
7
0
I7
1
I15
2
QI7
DI 16x24VDC HA
Equipment Manual, 10/2020, A5E39265608-AD
6
5
DI6
DI5
DI14
DI13
QDI6
QDI5
QDI14
QDI13
6
5
I6
I5
I14
I13
QI6
QI5
Drivers, parameters, diagnostics messages and address space
A.7 Address space of the time stamping (accuracy 1 ms)
4
3
DI4
DI3
DI12
DI11
QDI4
QDI3
QDI12
QDI11
4
3
I4
I3
I12
I11
QI4
QI3
2
1
DI2
DI1
DI10
DI9
QDI2
QDI1
QDI10
QDI9
2
1
I2
I1
I10
I9
QI2
QI1
0
DI0
DI8
QDI0
QDI8
0
I0
I8
QI0