Viessmann VITOCAL 151-A Installation And Service Instructions Manual page 99

Air source heat pump, monoblock version for heating and cooling operation, with 1 integrated heating/cooling circuit
Hide thumbs Also See for VITOCAL 151-A:
Table of Contents

Advertisement

Fault messages
(cont.)
Message code
System characteristics
F.100
Function of the electronics
modules connected to Plus-
Bus not available
F.101
Function of the electronics
modules connected to Plus-
Bus not available
F.102
No WiFi
F.103
No operation possible
F.104
Depending on configuration
of EM-EA1 extension (DIO
electronics module)
F.111
Refrigerant circuit off
F.112
Refrigerant circuit off
Cause
Short circuit, PlusBus
Voltage error PlusBus
Communication error, Wi-
Fi communication module
HMI programming unit
communication error
External fault message in-
put active
Lead break, liquid gas
temperature sensor, heat-
ing
Short circuit, liquid gas
temperature sensor, heat-
ing
Troubleshooting
Measures
Check PlusBus power supply at
HPMU electronics module: Iso-
late all PlusBus components con-
nected. Reconnect each one in
turn.
Check connections at plug 74 of
the HPMU electronics module.
Wall mounted indoor unit:
Check the connections at plug 74
on the connection socket on the
underside of the appliance.
Check whether there is a short
circuit at the PlusBus cables.
Isolate the system from the pow-
er supply. Restart the system.
If the fault persists, replace
HPMU electronics module.
Check PlusBus power supply at
HPMU electronics module: Iso-
late all PlusBus components con-
nected. Reconnect each one in
turn.
Check connections at plug 74 of
the HPMU electronics module.
Wall mounted indoor unit:
Check the connections at plug 74
on the connection socket on the
underside of the appliance.
Check whether there is a short
circuit at the PlusBus cables.
Isolate the system from the pow-
er supply. Restart the system.
If the fault persists, replace
HPMU electronics module.
Replace the WiFi communication
module.
Replace HMI programming unit.
Check the settings in the com-
missioning assistant for fault
message input. Adjust settings if
required.
Check connected external appli-
ance.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X21.1/X21.2 of the VCMU re-
frigerant circuit controller. Replace
sensor if required.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X21.1/X21.2 of the VCMU re-
frigerant circuit controller. Replace
sensor if required.
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents