Troubleshooting
Fault messages
(cont.)
Message code
System characteristics
F.832
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.833
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.834
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.835
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.836
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.837
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.838
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.839
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.841
Compressor running uneven-
ly.
F.843
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.845
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
F.846
Refrigerant circuit off: Inverter
and compressor cannot be
switched on.
108
Cause
Inverter temperature sen-
sor faulty
Inverter temperature sen-
sor faulty
Power supply on inverter
faulty
Unsuitable inverter or in-
verter incorrectly program-
med
Overvoltage fault on inver-
ter
Power supply on com-
pressor faulty
Control of inverter faulty
Compressor blocked
Excessive compressor
torque
Compressor power con-
sumption high
Overvoltage shutdown, in-
verter
Unsuitable inverter or in-
verter incorrectly program-
med
Compressor rotating field
counter-rotating
Measures
Isolate the system from the power
supply. Restart the system.
If the fault persists, replace the in-
verter.
Isolate the system from the power
supply. Restart the system.
If the fault persists, replace the in-
verter.
Check the power supply of the out-
door unit (compressor power sup-
ply).
If the fault persists, contact the
power supply utility.
Consult Viessmann Technical
Service.
Check power connection on
compressor.
If the fault persists, replace the
inverter.
If the fault persists, replace the
compressor.
Check the electrical connection
between inverter and compres-
sor.
If the fault persists, replace the
inverter.
Issue new demand to compres-
sor.
If the fault occurs frequently, re-
place the inverter.
Issue new demand to compres-
sor.
If the fault occurs frequently, re-
place the compressor.
Issue new demand to compres-
sor.
If the fault occurs frequently, re-
place the compressor.
Issue new demand to compres-
sor.
If the fault persists, replace the
compressor.
Isolate the system from the power
supply. Restart the system.
If the fault persists, replace the in-
verter.
Refer to type plate and order No.
to check whether correct part was
delivered and installed.
If the fault persists, replace the in-
verter.
Check phase connections on in-
verter.
Check compressor power supply.