Specification
Specification
(cont.)
Type AWOT-M-E-AC
Sound power of the outdoor unit at rated heat-
ing output
(Measurements with reference to EN 12102/
EN ISO 9614-2)
Assessed total sound power level at A7/W55
ErP
Max.
In night mode
Energy efficiency class to Commis-
sion Regulation (EU) No. 813/2013
Heating, average climatic conditions
Low temperature application (W35)
Medium temperature application
(W55)
Heating performance data to Commis-
sion Regulation (EU) No. 813/2013
(average climatic conditions)
Low temperature application (W35)
Energy efficiency
η
S
Rated heating output P
Seasonal coefficient of performance
(SCOP)
Medium temperature application (W55)
Energy efficiency
η
S
Rated heating output P
Seasonal coefficient of performance
(SCOP)
Heat pumps with 230 V~ outdoor unit
Type AWOT-M-E-AC
Heating performance data to EN 14511
(A2/W35)
Rated heating output
Power consumption
Coefficient of performance
heating mode (tolerance
Output control
Heating performance data to EN 14511
(A7/W35, 5 K spread)
Rated heating output
Fan speed
Air flow rate
Power consumption
Coefficient of performance
heating mode (tolerance
Output control
160
dB(A)
dB(A)
dB(A)
%
kW
rated
%
kW
rated
kW
kW
(COP) in
ε
5 %)
±
kW
kW
rpm
3
m
/h
kW
(COP) in
ε
5 %)
±
kW
151.A10
151.A13
56
66
59
+++
A
A
++
190
9.8
4.825
145
9.37
3.7
151.A10 SP
151.A13 SP
5.8
1.41
4.1
2.2 to 11.0
7.3
430
4045
1.46
5.0
2.6 to 12.0
151.A16
56
66
59
+++
A
A
++
178
12.4
4.525
141
12.1
3.6
151.A16 SP
6.7
1.76
3.8
2.6 to 12.3
3.0 to 13.7
8.1
440
4188
1.65
4.9
3.0 to 13.4
3.3 to 14.9
56
66
59
+++
A
A
++
178
13.67
4.525
141
13.37
3.6
7.6
2.00
3.8
9.1
567
5393
1.86
4.9

Hide quick links: