Electrical connection
Bottom PCB: 230 V~ function components and digital inputs
1 2 3 4 5 6 7 8 9 10 11 12 13 14
143
N
F2
L
40
1/N/PE
230 V/50 Hz
Fig. 40
Luster terminals for 230 V~ components and digital inputs
Terminals
Component/function
1 to 5
143.1
Power supply for configurable digital in-
puts 1 to 4
143.2
Configurable digital inputs 1 to 4
Possible functions: See chapter "Digital in-
143.3
put functions"
143.4
143.5
6 to 8
3-way diverter valve for heating water buf-
171.N
fer cylinder bypass with active cooling func-
171.
tion
171.L
AC
(cont.)
171
N
L N
AC
L1 L2 L3
136
r
3/N/PE 400 V/50 Hz
Installation sequence
P1
P2
L N
1
N
N1 N2 N3
136
r
3x
1/N/PE 230 V/50 Hz
C
Explanation
Voltage: 230 V~
Set the required parameters during commis-
sioning: See chapter "Commissioning assis-
tant"
Breaking capacity: 230 V~, 0.15 A
Recommended connecting cable:
2
2 x 0.75 mm
Max. cable length: 50 m
Output: 230 W
Voltage: 230 V~
Max. switching current: 1 A
Recommended connecting cable:
3 x 1.5 mm
2
Max. cable length: 50 m
C
L
49

Hide quick links:

Advertisement

Table of Contents
loading