Fault messages
(cont.)
Message code
System characteristics
F.687
The heat pump is switched
off.
No function of connected
components
F.770
Refrigerant circuit off
F.771
Refrigerant circuit off
F.772
Refrigerant circuit can only
be operated when outside
temperatures are above 5 °C
F.773
Refrigerant circuit can only
be operated when outside
temperatures are above 5 °C
F.788
No room heating/cooling
No DHW heating
F.790
No room heating/cooling
No DHW heating
F.791
Reduced output, instantane-
ous heating water heater
F.792
Reduced output, instantane-
ous heating water heater
Cause
EHCU electronics module
communication error
Lead break, flow tempera-
ture sensor, secondary cir-
cuit downstream of con-
denser
Short circuit, flow temper-
ature sensor, secondary
circuit downstream of con-
denser
Lead break, oil sump tem-
perature sensor
Short circuit, oil sump
temperature sensor
Fault, control and/or pow-
er supply of 4/3-way valve
Motor of 4/3-way valve
not correctly mounted
4/3-way valve faulty
Phase L1 in power supply
of instantaneous heating
water heater not present
Phase L2 in power supply
of instantaneous heating
water heater not present
Troubleshooting
Measures
Check connections on EH-
CU electronics module.
Check whether components are
wrongly connected.
Isolate the system from the pow-
er supply. Restart the system.
If the fault persists, replace the
EHCU electronics module.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X15.3/X15.4 of the VCMU re-
frigerant circuit controller. Replace
sensor if required.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X15.3/X15.4 of the VCMU re-
frigerant circuit controller. Replace
sensor if required.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X20.3/X20.4 of the VCMU re-
frigerant circuit controller. Replace
sensor if required.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X20.3/X20.4 of the VCMU re-
frigerant circuit controller. Replace
sensor if required.
Check connections on motor of
4/3-way valve.
Check motor of 4/3-way valve.
Replace motor if necessary.
Check mounting of motor: See
separate installation instructions.
Check hydraulic and electrical
connections of 4/3-way valve.
Check motor of 4/3-way valve.
Replace motor and/or 4/3-way
valve if required.
Check fuse for instantaneous
heating water heater.
Check power supply on instanta-
neous heating water heater and
on connections of indoor unit.
Check power cables.
Check instantaneous heating wa-
ter heater. Replace if required.
Check fuse for instantaneous
heating water heater.
Check power supply on instanta-
neous heating water heater and
on connections of indoor unit.
Check power cables.
Check instantaneous heating wa-
ter heater. Replace if required.
105