Outdoor unit maintenance
Checklist for maintenance work
Measure
Leak detection
aS
The following leak detection processes are suitable for appliances
with flammable refrigerant:
Leak detection with electronic refrigerant detectors:
Electronic refrigerant detectors may not have the required sensi-
tivity or may need to be calibrated to the relevant range. Carry
out the calibration in refrigerant-free surroundings.
The refrigerant detector must be suitable for the R290 refriger-
ant to be detected.
The refrigerant detector must not contain any potential ignition
sources.
Calibrate the refrigerant detector to the refrigerant used. Set the
response threshold to < 3 g/a, suitable for propane.
Leak detection with liquid leak detectors:
Liquid leak detectors are suitable for use with most refrigerants.
!
Please note
Liquid leak detectors containing chlorine may react with
the refrigerant. This could result in corrosion.
Do not use liquid leak detectors that contain chlorine.
Measures to take if a leak in the refrigerant circuit occurs or is
suspected:
Immediately extinguish all open flames in the vicinity of the heat
pump.
If brazing/soldering work needs to be undertaken to remedy the
leak, always extract all the refrigerant from the refrigerant circuit.
Purge the site to be brazed/soldered before and during the braz-
ing/soldering work with oxygen-free nitrogen.
Extracting the refrigerant
aD
Carry out the work in accordance with chapter "Extracting the re-
frigerant".
aF
Testing pressure resistance
Carry out the work according to chapter "Testing pressure resist-
ance".
Filling the refrigerant circuit
aG
Carry out the work in accordance with chapter "Filling the refriger-
ant circuit".
Shutdown
aH
Carry out the work in accordance with chapter "Final decommis-
sioning and disposal".
Identification (labelling the heat pump)
aJ
If the heat pump has been taken out of use, affix a label to the
outdoor unit in a clearly visible position containing the following in-
formation with date and signature:
Outdoor unit works with flammable refrigerant R290 (propane).
System has been taken out of use.
Refrigerant has been extracted.
Outdoor unit contains nitrogen.
Outdoor unit may contain residual flammable refrigerant.
140
(cont.)
Completed
Comments