Viessmann VITOCAL 151-A Installation And Service Instructions Manual page 106

Air source heat pump, monoblock version for heating and cooling operation, with 1 integrated heating/cooling circuit
Hide thumbs Also See for VITOCAL 151-A:
Table of Contents

Advertisement

Troubleshooting
Fault messages
(cont.)
Message code
System characteristics
F.793
Reduced output, instantane-
ous heating water heater
F.797
Secondary pump/heating cir-
cuit pump, heating/cooling
circuit 1 is off.
No room heating, heating/
cooling circuit 1
No DHW heating
F.798
Heating circuit pump, heat-
ing/cooling circuit 2 is off.
No room heating, heating/
cooling circuit 2
No DHW heating
F.799
Secondary pump/heating cir-
cuit pump, heating/cooling
circuit 1 is off.
No room heating, heating/
cooling circuit 1
No DHW heating
F.800
Heating circuit pump, heat-
ing/cooling circuit 2 is off.
No room heating, heating/
cooling circuit 2
No DHW heating
F.801
Fault, outdoor unit, no refrig-
erant circuit reversal
F.808
The refrigerant circuit will not
start.
F.812
The refrigerant circuit will not
start.
106
Cause
Phase L3 in power supply
of instantaneous heating
water heater not present
Secondary pump/heating
circuit pump, heating/cool-
ing circuit 1 is faulty
Heating circuit pump,
heating/cooling circuit 2 is
faulty
Secondary pump/heating
circuit pump, heating/cool-
ing circuit 1 is faulty
Heating circuit pump,
heating/cooling circuit 2 is
faulty
4-way diverter valve faulty
Lower fan not running.
Upper fan not running.
Measures
Check fuse for instantaneous
heating water heater.
Check power supply on instanta-
neous heating water heater and
on connections of indoor unit.
Check power cables.
Check instantaneous heating wa-
ter heater. Replace if required.
Isolate the system from the power
supply. Restart the system.
If the fault persists, replace secon-
dary pump/heating circuit pump,
heating/cooling circuit 1.
Isolate the system from the power
supply. Restart the system.
If the fault persists, replace heating
circuit pump, heating/cooling cir-
cuit 2.
Isolate the system from the power
supply. Restart the system.
If the fault persists, replace secon-
dary pump/heating circuit pump,
heating/cooling circuit 1.
Isolate the system from the power
supply. Restart the system.
If the fault persists, replace heating
circuit pump, heating/cooling cir-
cuit 2.
Check connections on VCMU re-
frigerant circuit controller.
Check 4-way diverter valve
(function check). Replace coil if
required.
Isolate the system from the pow-
er supply. Restart the system.
If the fault persists, replace the 4-
way diverter valve.
Check connections on VCMU re-
frigerant circuit controller.
Check fan can rotate freely.
Check lower fan via actuator test.
Isolate the system from the pow-
er supply. Restart the system.
If the fault persists, replace the
lower fan.
Check connections on VCMU re-
frigerant circuit controller.
Check fan can rotate freely.
Check upper fan via actuator
test.
Isolate the system from the pow-
er supply. Restart the system.
If the fault persists, replace the
upper fan.