Troubleshooting
Fault messages
(cont.)
Message code
System characteristics
F.1
The heat pump is switched
off.
F.2
The heat pump is switched
off.
F.3
No defrost
No room cooling
F.4
No defrost
No room cooling
F.7
Only room heating
No DHW heating
F.8
Only room heating
No DHW heating
F.13
An outside temperature value
of 0 °C is used to calculate
the set flow temperature.
96
Cause
Lead break, flow tempera-
ture sensor, secondary cir-
cuit / heating/cooling cir-
cuit 1
Short circuit, flow temper-
ature sensor, secondary
circuit / heating/cooling
circuit 1
Lead break, secondary
circuit return temperature
sensor
Short circuit, secondary
circuit return temperature
sensor
Lead break, cylinder tem-
perature sensor
Short circuit, cylinder tem-
perature sensor
Lead break, outside tem-
perature sensor
Measures
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X4.1/X4.2 of the EHCU elec-
tronics module. Replace sensor if
required.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X4.1/X4.2 of the EHCU elec-
tronics module. Replace sensor if
required.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X4.3/X4.4 of the EHCU elec-
tronics module. Replace sensor if
required.
Check resistance value
(NTC 10 k
) at connec-
Ω
tion X4.3/X4.4 of the EHCU elec-
tronics module. Replace sensor if
required.
Check resistance value
(NTC 10 k
). Replace sensor if re-
Ω
quired.
Wall mounted indoor unit:
Connection on the underside of
the appliance to 6-pole connec-
tion socket on the right, termi-
nals 9 and 10.
Floorstanding indoor unit:
Connection at plug 5 on the
HPMU electronics module
Check resistance value
(NTC 10 k
). Replace sensor if re-
Ω
quired.
Wall mounted indoor unit:
Connection on the underside of
the appliance to 6-pole connec-
tion socket on the right, termi-
nals 9 and 10.
Floorstanding indoor unit:
Connection at plug 5 on the
HPMU electronics module
Check resistance value
(NTC 10 k
). Replace sensor if re-
Ω
quired.
Wall mounted indoor unit:
Connection on the underside of
the appliance to 6-pole connec-
tion socket on the right, termi-
nals 11 and 12.
Floorstanding indoor unit:
Connection at luster terminals for
sensors, terminal 5 and 6