Viessmann VITOCAL 151-A Installation And Service Instructions Manual page 65

Air source heat pump, monoblock version for heating and cooling operation, with 1 integrated heating/cooling circuit
Hide thumbs Also See for VITOCAL 151-A:
Table of Contents

Advertisement

Power supply
(cont.)
Mains power supply in conjunction with self-consumption
Without power-OFF
Vitocal
A
F
G
kWh
L
M
N
Fig. 56
Heat pump
A
Additional consumers (of self-generated power) in
B
the household
Energy meter
C
Inverter
D
Isolator for the photovoltaic system
E
Terminal
F
Double-tariff meter (for special tariff for heat
G
pumps)
Not permissible in conjunction with photovoltaic
systems for self-consumption
Closing the indoor unit
Danger
The absence of system component earthing can
lead to serious injury from electrical current and
component damage in the event of an electrical
fault.
Before closing the indoor unit, restore all pro-
tective conductor connections.
Check whether equipment and pipe connec-
tions are connected to the equipotential bond-
ing of the building. Restore the connections if
required.
B
Vitocal
A
C
F
N
E1E2
D /D
F
L1 L1 L2 L2 L3 L3
H
kWh
L
N
~ ~
=
D
E
F
K
kWh
M
Bidirectional meter (for photovoltaic systems suita-
H
ble for self-consumption):
Energy drawn from power supply utility and energy
exported to power supply utility
Meter with reversing block:
K
For energy generated by the photovoltaic system
Isolator for domestic power supply connection (dis-
L
tribution panel)
Distribution panel
M
Domestic distribution box
N
!
Please note
If a casing door is not securely closed this can
lead to damage from condensation, vibrations
and excessive noise.
Check all-round seal of front panel for dam-
age.
Close appliance correctly.
On pipe and hose outlets, ensure the thermal
insulation is seated correctly.
Installation sequence
65