Specification
(cont.)
Type AWOT-E-AC
Heating performance data to Commis-
sion Regulation (EU) No. 813/2013
(average climatic conditions)
Low temperature application (W35)
Energy efficiency
η
S
Rated heating output P
rated
Seasonal coefficient of performance
(SCOP)
Medium temperature application (W55)
Energy efficiency
η
S
Rated heating output P
rated
Seasonal coefficient of performance
(SCOP)
Heat pumps with 230 V~ outdoor unit
Type AWOT-M-E-AC
Heating performance data to EN 14511
(A2/W35)
Rated heating output
Power consumption
Coefficient of performance
heating mode
Output control
Heating performance data to EN 14511
(A7/W35, 5 K spread)
Rated heating output
Fan speed
Air flow rate
Power consumption
Coefficient of performance
heating mode
Output control
Heating performance data to EN 14511
(A
7/W35)
Rated heating output
Power consumption
Coefficient of performance
heating mode
Air intake temperature
Cooling mode
Min.
Max.
Heating mode
Min.
Max.
151.A10
%
kW
%
kW
151.A10
kW
kW
(COP) in
ε
kW
kW
rpm
m
3
/h
kW
(COP) in
ε
kW
kW
kW
(COP) in
ε
°C
°C
°C
°C
151.A13
190
9.8
4.825
145
9.37
3.7
151.A13
5.8
1.41
4.1
2.2 to 11.0
2.6 to 12.3
7.3
430
4045
1.46
5.0
2.6 to 12.0
3.0 to 13.4
9.7
3.23
3.0
10
45
20
40
Specification
151.A16
178
178
12.4
13.67
4.525
4.525
141
141
12.1
13.37
3.6
3.6
151.A16
6.7
7.6
1.76
2.00
3.8
3.8
3.0 to 13.7
8.1
9.1
440
567
4188
5393
1.65
1.86
4.9
4.9
3.3 to 14.9
11.1
12.4
3.96
4.39
2.8
2.8
10
10
45
45
20
20
40
40