Troubleshooting Guide - Assa Abloy SECURITRON DEM680E Series Installation & Operating Instructions Manual

Delayed egress magnalock with ecomag technology
Table of Contents

Advertisement

Troubleshooting Guide

TROUBLE INDICATOR
Solid RED
Solid RED with
Audible Alarm
Solid AMBER
Flashing RED
LED off
Intermittent alarm
No alarm
* Failure means that the circut cannot detect a signal from the sensor. Check that the sensor connectors are properly
seated and inspect sensor wires for damage. Call Technical Support if replacement is needed.
POSSIBLE CAUSES
• Two bond sensor failures*
• Supply voltage < 8.5 VDC
• Two bond sensor failures*
• Open door
• DPS failure*
• Attempting to calibrate with two bond sensor failures*
• Strike tray installed upside down
• DPS magnet missing from strike tray
• Door sag
• Obstructed strike/magnet face
• Supply voltage < 10.8 VDC
• Single bond sensor failure*
• Magnet disconnected or magnet cable wire broken
• Verify that the strike label has been removed
• Factory reset
• LED disabled by SW1
• Supply voltage < 5 VDC
• Over-tightened strike screw
POSSIBLE SOLUTIONS
• Ensure bond sensor connectors are properly seated
• Check power supply voltage
• Ensure bond connectors are properly seated
• Close door
• Ensure DPS connector is properly seated
• Ensure bond connectors are properly seated
• Ensure that the strike tray is mounted
with alignment tabs facing up
• Check strike tray for damage, replace if needed
• Recalibrate
• Check for obstructions between strike and magnet
• Clean face of strike and magnet. Recalibrate
• Check power supply voltage
• Ensure bond connectors are properly seated
• Make sure magnet connector is properly
seated or repair magnet cable wire
• Ensure SW10 is in the OFF position
• Turn SW1 to the ON position
• Check power supply
• Unscrew strike screw 1/2 turn at a time
until alarm sound is constant when door
is pushed (Recalibrate lock after each
adjustment and repeat Install Verification)
11 of 12