Initial Calibration; Reinstalling The Cover - Assa Abloy SECURITRON DEM680E Series Installation & Operating Instructions Manual

Delayed egress magnalock with ecomag technology
Table of Contents

Advertisement

Initial calibration

NOTE 1: If calibration does not proceed according to the instructions
below, please see the troubleshooting section at the end of the manual.
NOTE 2: Initial calibration can be performed with a 12-V battery for
installations in facilities that do not yet have commercially-available power.
NOTE 3: Access control systems may register DPS and/or
BOND error conditions during the calibration sequence.
TECH TIP: For installation on a door without a door handle, a pull handle can
be made from masking or other tape to pull the door closed for calibration.
The DEM680E performs an automatic calibration
when the unit is initially powered up. This process only
proceeds if the door is closed and the unit has received
acceptable signals from the DPS and bond sensors.
PERFORM a manual calibration immediately
following installation, if necessary.
1
ENSURE that the door is closed.
2
APPLY power to the Magnalock.
3
PRESS AND RELEASE the calibration button (see Diagram 34).
4
VERIFY that the LED changes from red to amber
to green. The unit is now calibrated.

Reinstalling the cover

NOTE: After wiring, settings, and calibration have been
performed, and the system is functioning properly, the
cover may be reinstalled on the Magnalock.
1
PLACE the cover over the rear of the Magnalock
2
INSTALL the two (2) Phillips screws to
secure the cover (see Diagram 35).
3
APPLY the provided NFPA label with the appropriate
(15 or 30 second) delay designation to the door.
Diagram 34 Calibration button
Diagram 35 Reinstalling the cover
Calibration Button
9 of 12