Mounting and Dismounting

IMPORTANT
To allow the evaporation of any condensation resulting from low shipping / storage temperatures,
keep the controller at room temperature for at least 24hrs before applying power.
US requirement, only: This device must be installed in a UL-listed enclosure offering adequate
space to maintain the segregation of line voltage field wiring and Class 2 field wiring.
In the case of vertical mounting on DIN rails, the CIPer Model 50 controller should be secured in
place using a commercially available stopper. See also the CIPer Model 50 Mounting Instructions-
31-00234.

Dimensions

RS485-1
1
2
Figure 21: CIPer Model 50 controller (w/o HMI but with RJ45 socket for connection of portable HMI, and
Figure 22: CIPer Model 50 controller with covers, dimensions in inches (mm)
NOTE
Use of the covers (MVC-80-AC1) obstructs access to the Ethernet and USB 2.0 Host Interfaces and
RS232 socket
CIPer
MODEL 50 CONTROLLER – INSTALLATION AND COMMISSIONING INSTRUCTIONS
TM
8.4"
(215.5)
2
1
24 25 26
27 28 29 30 31 32
33 34 35 36 37
5
6
7
8
9 10
11 12 13 14 15 16 17 18
with full complement of onboard I/Os), dimensions in inches (mm)
8.4"
(215.5)
J1
J8
38 39
40 41 42 43 44 45 46 47
1.8"
(45)
19 20 21 22 23
29
2.4"
(57.5)
1.94"
(49.5)
2.05"
(52)
2.4"
(57.5)
2.05"
(52)
31-00233-02