MODEL 50 CONTROLLER – INSTALLATION AND COMMISSIONING INSTRUCTIONS
TM

Transformer Data

In the U.S. and Canada, if the CIPer Model 50 is powered by transformers, then such transformers must be
NEC Class-2 transformers. In Europe, if the CIPer Model 50 is powered by transformers, then such
transformers must be safety isolating transformers conforming to IEC61558-2-6.
Part # 1450 7287
-001
-002
-003
-004
-005
-006
Transformer
CRT 2
CRT 6
CRT 12
NOTE
An Uninterruptable Power Supply can be directly wired to a CIPer Model 50 controller.
31-00233-02
Table 9. 1450 series transformers data
Primary side
120 VAC
120 VAC
120 VAC
240/220 VAC
240/220 VAC
240/220 VAC
Table 10. Overview of CRT Series AC/DC current
Primary side
Max. AC current
230 VAC
230 VAC
230 VAC
Figure 25: Connection of CIPer Model 50 controller
Secondary side
24 VAC, 50 VA
2 x 24 VAC, 40 VA, 100 VA from separate
transformer
24 VAC, 100 VA, 24 VDC, 600 mA
24 VAC, 50 VA
2 x 24 VAC, 40 VA, 100 VA from separate
transformer
24 VAC, 100 VA, 24 VDC, 600 mA
2 A
6 A
12 A
34
Max. DC current
500 mA
1300 mA
2500 mA