Wiring Terminals
The CIPer Model 50 is equipped with push-in terminal plugs.
NOTE
• With solid conductors, ferrules are prohibited.
• Use only one conductor per push-in terminal.
• If, nevertheless, two stranded wires are to be connected to a single push-in terminal, twin wire
end ferrules must be used.
Plug gauge
Solid conductor H05(07) V-K
Stranded conductor H05(07) V-K
Stranded conductor with wire end ferrules (w/o
plastic collar)
Stripping length
Terminal Assignment
Terminal
Signal
no.
1
24V-0
2
24V~
3,4
-
5
BO1
6
BO2
7
BO3
8
IN1,2,3
9
INX
10
BO4
11
BO5
12
IN5
13
IN6
14
BO6
CIPer
MODEL 50 CONTROLLER – INSTALLATION AND COMMISSIONING INSTRUCTIONS
TM
Figure 23: Inserting/removing wires from push-in terminals
Table 7. CIPer Model 50 push-in terminal wiring specifications
Table 8. Terminal assignment
Supply voltage (GND), int. connected with term. 31 and system
GND (term. 19+37)
supply voltage (24V)
Not used
Binary output 1. N.O. relay contact switching input power
connected to terminal 8
Binary output 2. N.O. relay contact switching input power
connected to terminal 8
Binary output 3. N.O. relay contact switching input power
connected to terminal 8
Common relay contact for BO1, BO2, and BO3
Relay contact for BO4
Binary output 4. N.O. relay contact switching input power
connected to terminal 9
Binary output 5. N.O. relay contact switching input power
connected to terminal 12
Relay contact for BO5
Relay contact for BO6
Binary output 6. N.O. relay contact switching input power
connected to terminal 13
0.0003... 0.002" (0.2 ... 1.50 mm)
0.0003... 0.002" (0.2 ... 1.50 mm)
0.0003... 0.002" (0.2 ... 1.50 mm)
0.0003... 0.002" (0.2 ... 1.50 mm)
0.4" + 0.04" (10.0 +1.0 mm)
Description
31
WEB-
EHSERIESNX26XX
X
X
-
X
X
X
X
X
X
X
X
X
X
31-00233-02