Setting the I/O Bus Switch

Set the I/O Bus switch S2 of the XCL8010AU Controller
Module depending on the modules connected to terminals
71 ─ 78 and the desired communication as follows:
Table 10. I/O Bus switch settings
communication
S2 setting
L
W
Bus
LON
ON
ORKS
only
Panel Bus and
Panel
L
W
Bus
ON
ORKS
Fig. 15. S2 I/O Bus switch
EN1B-0410GE51 R0908A
4
4
W
Bus I/O modules,
ON
ORKS
terminals
71 ─ 74 L
W
Bus
ON
ORKS
75 ─ 78 L
W
Bus
ON
ORKS
11 ─ 14 L
W
Bus
ON
ORKS
71 ─ 74 Panel Bus
75 ─ 78 Panel Bus
11 ─ 14 L
W
Bus
ON
ORKS
L
W
Bus Topologies
ON
ORKS
The L
W
Bus is a 78-kilobit serial link that uses
ON
ORKS
transformer isolation so that the bus wiring does not have a
polarity. I.e. it is not important which of the two L
Bus terminals are connected to each wire of the twisted pair.
The L
W
Bus does not need to be shielded on the
ON
ORKS
controller module side.
The L
W
Bus can be wired in daisy chain, star, loop or
ON
ORKS
any combination thereof as long as the maximum wire length
requirements are met.
Configuration
The recommended configuration is a daisy chain with two bus
terminations. This layout allows for max. L
lengths, and its simple structure presents the least number of
possible problems, particularly when adding on to an existing
bus.

C-Bus Topologies

Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.)
can communicate with one another and a PC central. The C-
Bus must be connected via the individual controllers (open
ring).
NOTE:
Star connection is not allowed because
uncontrollable line reflections may occur.
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet.
Disconnect the power supply before you start to install the
Excel 800 System.
More than one disconnect switch may be required to de-
energize the system.
Do not reconnect the power supply until you have
completed the installation.
NOTE:
The terminal socket of each I/O module can be
mounted and wired before inserting and locking
the corresponding electronic module.
14