Mounting/Dismounting Modules
LOCK
Fig. 14. HEX switch location
NOTE:
If the HEX switch setting is changed, the Panel
Bus I/O module will revert to its default
configuration. With L
the HEX switch is without function.
Setting the I/O Bus Switch
Set the I/O Bus switch S2 of the XCL8010AU Controller
►
Module depending on the modules connected to terminals
71 ─ 78 and the desired communication as follows:
Table 10. I/O Bus switch settings
communication
S2 setting
L
W
Bus
LON
ON
ORKS
only
Panel Bus and
Panel
L
W
Bus
ON
ORKS
Fig. 15. S2 I/O Bus switch
EN1B-0410GE51 R0908A
4
4
W
Bus I/O modules,
ON
ORKS
terminals
71 ─ 74 L
W
Bus
ON
ORKS
75 ─ 78 L
W
Bus
ON
ORKS
11 ─ 14 L
W
Bus
ON
ORKS
71 ─ 74 Panel Bus
75 ─ 78 Panel Bus
11 ─ 14 L
W
Bus
ON
ORKS
L
W
Bus Topologies
ON
ORKS
The L
W
Bus is a 78-kilobit serial link that uses
ON
ORKS
transformer isolation so that the bus wiring does not have a
polarity. I.e. it is not important which of the two L
Bus terminals are connected to each wire of the twisted pair.
The L
W
Bus does not need to be shielded on the
ON
ORKS
controller module side.
The L
W
Bus can be wired in daisy chain, star, loop or
ON
ORKS
any combination thereof as long as the maximum wire length
requirements are met.
Configuration
The recommended configuration is a daisy chain with two bus
terminations. This layout allows for max. L
lengths, and its simple structure presents the least number of
possible problems, particularly when adding on to an existing
bus.
C-Bus Topologies
Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.)
can communicate with one another and a PC central. The C-
Bus must be connected via the individual controllers (open
ring).
NOTE:
Star connection is not allowed because
uncontrollable line reflections may occur.
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet.
►
Disconnect the power supply before you start to install the
►
Excel 800 System.
More than one disconnect switch may be required to de-
energize the system.
Do not reconnect the power supply until you have
►
completed the installation.
NOTE:
The terminal socket of each I/O module can be
mounted and wired before inserting and locking
the corresponding electronic module.