Honeywell CIPer 50 Installation & Commissioning Instructions page 76

Hide thumbs Also See for CIPer 50:
Table of Contents

Advertisement

CIPer
MODEL 50 CONTROLLER – INSTALLATION AND COMMISSIONING INSTRUCTIONS
TM
NTC 20 kΩ (Type II) Temperature
Temp.
Temp.
[°F]
[°C]
77
25
78.8
26
80.6
27
82.4
28
84.2
29
86
30
87.8
31
89.6
32
91.4
33
93.2
34
95
35
96.8
36
98.6
37
100.4
38
102.2
39
104
40
105.8
41
107.6
42
109.4
43
111.2
44
113
45
114.8
46
116.6
47
118.4
48
120.2
49
31-00233-02
Terminal
Resistance
voltage [V]
20
4.22
19.1
4.12
18.2
4.01
17.4
3.91
16.6
3.81
15.9
3.71
15.2
3.62
14.5
3.52
13.9
3.43
13.3
3.33
12.7
3.24
12.1
3.15
11.6
3.06
11.1
2.97
10.7
2.89
10.2
2.81
9.78
2.72
9.37
2.64
8.98
2.57
8.61
2.49
8.26
2.42
7.92
2.34
7.6
2.27
7.29
2.2
7
2.14
NTC 20 kΩ (Type II) Temperature
Temp.
Temp.
[°F]
[°C]
257
125
258.8
126
260.6
127
262.4
128
264.2
129
266
130
267.8
131
269.6
132
271.4
133
273.2
134
275
135
276.8
136
278.6
137
280.4
138
282.2
139
284
140
285.8
141
287.6
142
289.4
143
291.2
144
293
145
294.8
146
296.6
147
298.4
148
300.2
149
302
150
76
Terminal
Resistance
voltage [V]
0.53
0.207
0.51
0.201
0.5
0.196
0.49
0.191
0.47
0.186
0.46
0.181
0.45
0.176
0.43
0.171
0.42
0.167
0.41
0.162
0.4
0.158
0.39
0.154
0.38
0.15
0.37
0.146
0.36
0.142
0.35
0.139
0.34
0.135
0.33
0.132
0.32
0.128
0.32
0.125
0.31
0.122
0.3
0.119
0.29
0.116
0.29
0.113
0.28
0.11
0.27
0.107