CIPer
MODEL 50 CONTROLLER – INSTALLATION AND COMMISSIONING INSTRUCTIONS
TM
Example 2: Multiple CIPer Model 50 Controllers and Connected BACnet Modules
Figure 46: Connection of multiple CIPer Model 50 controllers via their RS485-1 interfaces to a BACnet
Example 3: Multiple CIPer Model 50 Controllers and Connected BACnet Modules (with inserted
termination resistor)
Figure 47: Connection of multiple CIPer Model 50 controllers via their RS485-1 interfaces to a BACnet
The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module (in
this example, that is the rightmost CIPer Model 50, the 3-position slide switch of which has been set to
"BIAS.")
31-00233-02
MS/TP Bus
MS/TP Bus