Procedure - Siemens SICAM P 7KG7750 Manual

Power meter
Hide thumbs Also See for SICAM P 7KG7750:
Table of Contents

Advertisement

6

6.3 Procedure

6.3
Procedure
First, connect the SICAM P as described in chapter 6.2.
You can adjust the device manually or via programming software
Procedure at the device
Select Basic settings → Connection / Transformer.
Select the range to be adjusted (e.g. AC 228 V).
In the menu, select: Calibrate.
A dialog window appears.
Enter the setpoint value for adjustment voltage and adjustment current. Default setpoints are
the nominal ranges of the measuring ranges set under Connection / Transformer. Optimal
precision can be achieved by using these default setpoint values. If the default values are not
available, make the appropriate changes.
Switch the adjusting device on with the setpoints.
Follow the instructions. SICAM P is readjusted.
Procedure for programming software
Establish the communication between device and programming software.
In the menu, select: Calibration
A dialog window appears.
Select the element you wish to adjust: U or I
Enter the setpoints for adjustment of voltage and current. The setpoints given are the nominal
values of the measurement ranges set under Connection / Transformer. These preset set-
points ensure optimum precision. If the preset values are not correct, change them accord-
ingly.
Switch the adjusting device on with the setpoints.
Follow the instructions. SICAM P is readjusted.
130
Calibration of the
selected input range.
Please follow the in-
structions in manual!
<ok
<cancel
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013