4.4 Basic Settings
Caution
You must make these settings for a direct connection or for a connection with current trans-
formers.
The selected measuring range must be greater than the secondary rating of the current
transformer!
The accuracy of SICAM P (see table 3-3) is based on the selected measuring range.
The determination of this range indicates the maximum current value that can be displayed
on the device.
Note
When you change the current transformer settings, the power calculation in the device has to be
reset.
Example
CT rating: 500 / 1 A
Measuring range 1.2 A:
Measuring range 6 A:

4.4.2.2 Voltage Transformer

Yes:
Voltage transformers are utilized (max. primary: AC 1000 kV, secondary: AC 600 V)
No:
Voltage transformers are not utilized
Measuring range
132 V
228 V
480 V
828 V
62
Maximum display range: AC 0 A to 600 A
Maximum display range: AC 0 A to 3000 A
*voltage transf.:No
*meas. range L-L 480V
<ok
<cancel
nominal input AC 100/110 V
nominal input AC 190 V
nominal input AC 400 V
nominal input AC 690 V
kV/
V
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013