2. Confirm by clicking OK.
3. Query the device identification once to check the connection. To do this, click the ID symbol
in the toolbar.
4. Click the Receive Identification button to retrieve data from the device. If the configuration
is correct, all lines are filled with device data. Close the dialog window.
5. From the menu bar, select Device → Send new firmware.
6. In the Send firmware dialog, enter the path to the firmware (file 7KG*.SX)
7. Click the button Transmit firmware. The transfer may take some minutes. Check the ID
again (symbol ID, see item 3). The new firmware version will be displayed.
Note
A check sum allows to relate each firmware version to device types and hardware versions. This
ensures that no incompatible hardware and software version are updated. In this case, the trans-
fer will be terminated with the message "Timeout while waiting for reply from device". The original
firmware in the device remains unchanged.
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
5
5.10 Updating the Firmware