5.8.1
Options
You can set more parameters for the SICAM P under Options.
Regional settings
•
Language: Here, you can select what language the device display is in when you parame-
terize it using the device buttons.
•
Measured value designation: The description of the conductor on device L1/L3/L3 or A/B/
C can be selected here.
Power calculation
Here, you can select the type of power calculation and the calculation for current and voltage.
The basic setting is standard. Settings options:
•
Standard: All measured values are true RMS, taking all harmonics into consideration. Cal-
culation of reactive power using methods used by traditional measuring devices. (electrody-
namics power measurement)
•
DIN: All measured values are true RMS, taking all harmonics into consideration. Customized
from standard: reactive power calculation, apparent power calculation, cos φ and power fac-
tor, taking into consideration the new definition of apparent power in: DIN 40110-2.
•
Fourier: All measured values calculated from the fundamental wave. Harmonics are not con-
sidered.
Direction of current
•
Standard: Default setting for correct connection according to standard and back panel mark-
ing
•
Inverse: Current direction is negated (change the current direction to avoid changing the
connectors).
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
5
5.8 Additionals
101