Appendix A.3. Bacnet/Ip: Setting Network_Number For More Than One Protonode On Subnet; Appendix A.4. Led Diagnostics For Modbus Rtu Communications Between Protonode And Devices; Figure 25: Web Configurator Showing Setting The Network Number For Bacnet/Ip; Figure 26: Diagnostic Leds - FieldServer Protocessor ProtoNode FPC-N34 Startup Manual

Hide thumbs Also See for Protocessor ProtoNode FPC-N34:
Table of Contents

Advertisement

Triangle Tube's ProtoNode Startup Guide

Appendix A.3. BACnet/IP: Setting Network_Number for more than one ProtoNode on Subnet

On the main Web Configurator screen, update the Network Number in the Network_Nr and hit Submit. Please
note that the default value is 50.

Figure 25: Web Configurator showing setting the network number for BACnet/IP

Appendix A.4. LED Diagnostics for Modbus RTU Communications Between ProtoNode and Devices

Please see the diagram below for ProtoNode FPC-N34 and FPC-N35 LED Locations.
L
SP
Tag
SPL
The SPL LED will light if the ProtoNode is off line.
RUN
The RUN LED will start flashing 20 seconds after power indicating normal operation.
The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light
ERR
will indicate there is a system error on ProtoNode. If this occurs, immediately report the related "system error"
shown in the error screen of the GUI interface to FieldServer Technologies for evaluation.
RX
The RX LED will flash when a message is received from the boiler.
TX
The TX LED will flash when a message is sent to the boiler.
PWR
This is the power light and should show steady green at all times when ProtoNode is powered.
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com
Diagnostic LEDs
Description

Figure 26: Diagnostic LEDs

Email: support@protocessor.com
Page 31 of 40

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Protocessor ProtoNode FPC-N34 and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Protocessor protonode fpc-n35

Table of Contents