Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-112 Gamewell-FCI 7100 Series APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after April 2011 A Sierra Monitor Company Driver Version: 1.01 Document Revision:...
The FCI 7100 Series System Control Units are manufactured by Fire Control Instruments. A 7100 with an enabled serial port can transmit data to a FieldServer which can, in turn, make the data available to other devices including those which communicate using different protocols (e.g. BACnet) This passive Client driver does not poll for data, nor does it send data or commands to the 7100.
FCI Panel must be equipped with a PTRN module for isolation of the serial port. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com Party Equipment...
CONFIGURING THE FIELDSERVER AS A GAMEWELL-FCI 7100 SERIES CLIENT For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv”...
CONFIGURING THE FIELDSERVER AS A GAMEWELL-FCI 7100 SERIES SERVER The Server side of the driver is intended to support FieldServer’s Quality Assurance program and is not intended to provide complete emulation of a 7100 and is thus not fully documented. Should you require the Server side functionality to be documented and enhanced, please contact FieldServer’s sales group.
Manual synchronization is required. Push the reset button on the panel. This transmits a reset message to the FieldServer, which clears the data in the FieldServer. After a reset the panel sends messages to report all abnormal states. When all these messages have been processed the FieldServer and panel will be synchronized. This process can be repeated at any time.
FCI7100:#12b Err. No MD's to store message data." FCI7100:#13 Err. Msg was ignored. MD Required for Storage. Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com...
Page 16
FCI7100:#32 Err. No MD Length. Default to 1 FCI7100:#33 Err. Driver cant poll or write. Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com...
FCI7100:#36 Err. Too Short. Bytes=%d , conn->ux_iptr" Appendix B.2. Driver Stats Exposed. In addition to the standard FieldServer operating statistics the driver exposes certain key stats in a Data Array if required. A Server Side device can then monitor these stats.
#define FCI_7100_STAT_NODE_INFO_MSG #define FCI_7100_STAT_NO_PLACE_TO_STORE_NODE FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com Offset Description Increments each time a message is received Increments each time a character is recieved from the panel.
Need help?
Do you have a question about the Gamewell FCI 7100 Series and is the answer not in the manual?