Trunk Line And Drop Line Length; Trunk Line - YASKAWA SI-N3 Installation Manual

Devicenet ac drive option
Hide thumbs Also See for SI-N3:
Table of Contents

Advertisement

Option
*1
*1
PG-B3
, PG-X3
*1 *3 *4
PG-RT3
, PG-F3
*5
*5
DO-A3
, AO-A3
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3,
*4
*4
SI-W3
, SI-EM3
, SI-EM3D
*4
*4
EN3
, SI-EN3D
, SI-EP3, JOHB-
SMP3,
*5 *6
*5 *6
AI-A3
, DI-A3
*1
Not available for GA500 or FP605 drives.
*2
To connect two PG options, use the CN5-C and CN5-B connectors. To connect only one PG option, use the
CN5-C connector.
*3
If you use the motor switching function, you cannot use this option.
*4
Not available for 1000-Series drive models with capacities between 450 and 630 kW (650 to 1000 HP).
*5
Not available for GA500 drives.
*6
To use AI-A3 and DI-A3 input statuses as monitors, connect the options to CN5-A, CN5-B, or CN5-C.
9

Trunk Line and Drop Line Length

Refer to the ODVA website (www.odva.org) for more information on network cabling.

Trunk Line

The maximum allowable trunk line length depends on the type of cable used and the
network baud rate. The total cable length includes the length of the trunk and the sum of
all the drop lines.
Baud Rate (kbps)
125
250
500
To calculate the maximum total length for trunk lines of mixed thick and thin cables, use
the following formulas:
• 125 kbps: L
+ (5 x L
thick
• 250 kbps: L
+ (2.5 x L
thick
• 500 kbps: L
+ L
thick
YASKAWA TOEP C730600 84A DeviceNet Installation Manual
Table 8.1 Option Compatibility
*1 *3 *4
*4
, SI-
Table 9.1 Trunk Line Cable Length
Thick Cable
500 m (1640 ft)
250 m (787 ft)
100 m (328 ft)
) ≤ 500 m (1640 ft)
thin
) ≤ 250 m (1640 ft)
thin
≤ 100 m (328 ft)
thin
9 Trunk Line and Drop Line Length
Connector
CN5-B, CN5-C
CN5-C
CN5-A, B, and C
CN5-A
Number of Options
Possible
*2
2
1
1
1
Thin Cable
100 m (328 ft)
100 m (328 ft)
100 m (328 ft)
57

Advertisement

Table of Contents
loading

Table of Contents