Option Connection Diagram

*1
Connect the included ground wire for installations on 1000-series, GA500, and FP605 drives. The ground
wire is not necessary for installations on GA700 or GA800 drives.

Communication Cable Wiring

Route the option wiring as specified by these procedures.
Note:
Use only a DeviceNet dedicated communication cable. Refer to
for more information about selecting trunk line and drop line lengths. Refer to the ODVA website (www.odva.
org) for more information on network cabling.
 
1.
Prepare the communication cables as shown in
A - Sheath
B - Shield
YASKAWA TOEP C730600 84A DeviceNet Installation Manual
Figure 5.27 Option Connection Diagram
Figure 5.28 Prepare Ends of Shielded Cable
Trunk Line and Drop Line Length on page 57
Figure
5.28.
C - Use electrical tape or shrink
tubing to insulate the cable.
D - Shield
5 Installation Procedure