7 Configuring DeviceNet Messaging

No.
Name
(Hex.)
U6-97
OPT SPARE 4
(07F7)
U6-98
First Fault
(07F8)
U6-99
Current Fault
(07F9)
7
Configuring DeviceNet Messaging
This section provides information on the methods used to control the drive on DeviceNet.

Drive Polled Configuration on DeviceNet

You must configure the drive DeviceNet polled connection before you can receive
commands from a master device. Set these two parameters:
• F6-52 [Polled Consuming Assembly] (PCA)
Note:
This is the output assembly consumed by the drive.
• F6-53 [Polled Producing Assembly] (PPA)
Note:
This is the input assembly produced by the drive.
50
Description
Note:
The drive is compatible with option software versions
1111 and later.
Shows option software version.
Shows first option fault.
0 : No Fault
1 : Option Failure
2 : PLC in Idle State
3 : Force Fault
1000 : Network Power Loss
1001 : Connection Timeout
1002 : Duplicate MAC ID
1003 : Bus-off
Shows current option fault.
0 : No Fault
1 : Option Failure
2 : PLC in Idle State
3 : Force Fault
1000 : Network Power Loss
1001 : Connection Timeout
1002 : Duplicate MAC ID
1003 : Bus-off
YASKAWA TOEP C730600 84A DeviceNet Installation Manual
Default
(Range)
-
-
-