6 Related Drive Parameters

U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: Check the back cover of these manuals.
For questions, contact Yaskawa or a Yaskawa representative.
Note:
Download the EDS file for SI-N3 option. The SI-N3 will not function as a slave in the network without the
appropriate EDS file.
6
Related Drive Parameters
These parameters set the drive for operation with the option. Make sure that the parameter
settings in this table are correct before you start network communications.
Note:
Hex.: MEMOBUS addresses that you can use to change parameters over network communication are
represented in hexadecimal numbers.
No.
Name
(Hex.)
b1-01
Frequency
Reference
(0180)
Selection 1
b1-02
Run Command
Selection 1
(0181)
44
Description
Selects the input method for frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Note:
• To start and stop the drive with the DeviceNet master
device using serial communications, set b1-02 = 3 [Run
Command Selection 1 = Option PCB] or set the Net
Control bit in the assemblies or Control Supervisor
Object. To control the frequency reference of the drive
via the master device, set b1-01 = 3 or set the Net
Reference bit in the assemblies or AC/DC object.
• The default setting is different for different drives. Refer
to the instruction manual of your specific drive for more
information.
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
Note:
To start and stop the drive with the DeviceNet master
device using serial communications, set b1-02 = 3 or set
YASKAWA TOEP C730600 84A DeviceNet Installation Manual
Default
(Range)
1
(0 - 4)
1
(0 - 3)