Control Panel Terminal Blocks; 1: N16 With Slm-318 Signaling Loop Module; 2: Nfs2-3030 And Nfs-3030 With Lcm-320, Lem-320 - Honeywell NOTIFIER SLC Wiring Manual

Intelligent control panel
Table of Contents

Advertisement

Control Panel Terminal Blocks

2.4 Control Panel Terminal Blocks
2.4.1 N16 with SLM-318 Signaling Loop Module
N16 supports from one to ten SLC loops. Connect from one to three PMB-AUX Power Module Boards to the panel, and connect from
one to five SLM-318 Signaling Loop Modules to each PMB-AUX. Loops can be either CLIP mode or FlashScan mode. SLC Loops con-
nect to TB1 on the SLM-318.
Connections are the same on current SLM-318 (silkscreened "CLP-2PCB") and initial release (silkscreened "CLP-PCB").
2.4.2 NFS2-3030 and NFS-3030 with LCM-320, LEM-320
The NFS-3030/NFS2-3030 supports up to five pairs of loop control and expander modules, providing from one to ten SLC loops. Loops
can be either CLIP mode or FlashScan mode. SLC loops connect to TB1 on the LCM-320 or LEM-320.
Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021
SLC channel B
(output loop)
SLC Terminal Block
B+
Figure 2.4 Measuring the Wire Length of a Four-Wire SLC
Figure 2.5 N16 with SLM-318: SLC Loop Connections and Wiring
SLC Loop Connections
on Loop Control Modules
Figure 2.6 NFS2-3030, NFS-3030 SLC Loop Connections and Wiring
SLC channel A
(return loop)
A+
B–
A–
B+ A+ B- A-
TB1
SLC Loop Connections
on SLM-318 Modules
SLC Loop Connections
on Loop Expander Module
Wiring Requirements
23