7-3-2 Selection from input current

Use the following table to select the contactors so the total input current for each unit does not exceed
the rated continuity current.
SVJ2 total output capacity 1.5kW or less 3.5kW or less
Input current
MDS-B-SPJ2
Input current
Converter unit
Input current
Contactor rated continuity
current
(Total input current)
Recommended contactor
(Mitsubishi Electric Corp.:
Option part)
(Example 2)
The contactor is selected for the MDS-B-SVJ2-10 with 4 HC102 axes and an MDS-C1-CV-55
connected.
< Selection from rush current >
(SVJ2-10 × 4 axes rush current) + (MDS-C1-CV-55 rush current) = 4 × 100A + 15A
= 415A
Therefore, S-K50 200VAC.
< Selection from input current >
(HC102 × 4 axes input current) + (MDS-C1-CV-55 input current) = 30A + 30A = 60A
Therefore, S-N35 200VAC.
From these, the S-K50 200VAC is selected as having the larger of the two capacities.
Chapter 7 Peripheral Devices
Input current table
10A
20A
MDS-B-SPJ2-02
MDS-B-SPJ2-22
MDS-B-SPJ2-04
MDS-B-SPJ2-075
MDS-B-SPJ2-37
MDS-B-SPJ2-15
10A
20A
MDS-C1-CV-37
MDS-A-CR-10
MDS-A-CR-22
MDS-A-CR-15
MDS-A-CR-37
10A
20A
Contactor selection table 2
20A
S-N10
AC200V
7kW or less
10kW or less
30A
40A
MDS-B-SPJ2-55
MDS-B-SPJ2-75
30A
MDS-C1-CV-55
MDS-C1-CV-75
MDS-A-CR-55
MDS-A-CR-75
30A
32A
50A
S-N20
S-N25
AC200V
AC200V
7-5
13kW or less
16kW or less
50A
60A
MDS-B-SPJ2-110
40A
50A
MDS-A-CR-90
MDS-C1-CV-110
40A
50A
60A
S-N35
AC200V