4.2.1 External Alarm Output interface

FACP
Digital Board
Fire Alarm Control Panel
External Alarm Name
Donor Antenna Malfunction
Active RF Device Malfunction
Low Battery Capacity (70% depleted)
System Component Malfunction
Normal AC Power
Loss of Normal AC Power
Battery Charger Failure
Summary Alarm
Donor Antenna Disconnect
Oscillation Alarm
Annunciator Disconnect
Advanced RF Technologies, Inc.
24V DC
Set Condition
UL Return Power Hard Fail
-
RF Power Soft Fail
-
DL Return Power Hard Fail
-
DL/UL Over Power Hard Fail
-
DL/UL Input Overload Hard Fail
-
Low Battery Soft Fail
-
Over Current Hard Fail
-
Over Temperature Hard Fail
-
DSP Hard Fail
-
Out-band Overload Hard Fail
-
AC Normal Set
-
AC Fail Soft Clear
-
AC Fail Soft Set
-
AC Normal Clear
-
Battery Fail Soft Fail
-
Battery Not Connected Soft fail
-
Battery Not Charge Soft Fail
-
Any Active Alarm
-
No DL Signal Detected
-
Oscillation Hard Fail
-
Annunciator Disconnect Hard Fail
-
ADRF
Digital Board
ADRF PSR Repeater
Likely Causes
Damaged Donor Antenna
-
Degrading Amplifier
-
Open or Disconnected Server Port
-
Oscillation
-
Strong RF Input Signal
-
Battery Depleted
-
Faulty or Damaged PSU
-
Ambient Temperature
-
DSP Filter Fault
-
Strong RF Input Signal
-
Powered by AC Power
-
Powered by DC Power
-
Powered by DC Power
-
Powered by AC Power
-
Low Battery Charging Voltage
-
Battery Cable Disconnected
-
Degraded Batteries
-
Any Active Alarm Present in the System
-
Disconnected Donor Line
-
Gain Set Too High or Lack of Isolation
-
Disconnected PSR-ANN
-