Type Of Seating: Set - AUMA SQ 05.2 Operation Instructions Manual

Control unit - electromechanical with actuator controls
Hide thumbs Also See for SQ 05.2:
Table of Contents

Advertisement

Commissioning (basic settings)
10.2.

Type of seating: set

Limit
Torque
Select main menu
Select parameter
CLOSE or OPEN
54
SQ 05.2
SQ 14.2/SQR 05.2
3.
If the valve end position is not reached:
Slightly turn setting screw [2] counterclockwise until valve end position
OPEN can be safely set.
Turning the setting screw [2] clockwise results in a smaller swing angle.
Turning the setting screw [2] counterclockwise results in a larger swing
angle.
4.
Turn setting screw [2] clockwise to the stop.
This completes the setting of end stop OPEN.
5.
Check O-ring of screw plug for seat and condition, replace if damaged.
6.
Fasten and tighten screw plug [1].
Having completed this procedure, the end position detection OPEN can be set
immediately.
Valve damage due to incorrect setting!
The type of seating setting (limit or torque seating) must match the selection for
the valve.
Only change the setting with prior consent of the valve manufacturer.
Customer settings M0041
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
Default value: Limit
Setting values:
Seating in end positions via limit switching.
Seating in end positions via torque switching.
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: Press
Display indicates: End position CLOSED
4.
Use
Up ▲ Down ▼ to select:
▶ End position CLOSED
▶ End position OPEN
The black triangle ▶ indicates the current selection.
SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Profinet
to parameter, or
and enter ID M0086 or M0087

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents