Electrical connection
30
SQ 05.2
SQ 14.2/SQR 05.2
Figure 25: Profinet connection board with RJ-45 connections
n 1
Profinet cable from previous device
n+1
Profinet cable to next device
(For line topology or redundant ring/MRP - Media Redundancy Protocol)
Profinet connection is made via RJ-45 ports by means of connectors for field
assembly. The scope of delivery includes one RJ-45 Profinet connector for Cat.5
(supplied within electrical connector). Further connectors are available with AUMA
(e.g. for line topology or redundant ring) on request.
Order designations:
RJ-45 Profinet connector for Cat.5 (as included in scope of delivery): AUMA
article number K009.706
Option: RJ-45 Profinet connector for Cat.6
K009.705
Table 19:
Assignment of RJ-45 Profinet port
Signal
Function
TD +
Transmit Data +
TD
Transmit Data
RD +
Receive Data +
RD
Receive Data
Description of LEDs on connection board
Table 20:
MODS (Module Status)
Red LED: off +
Green LED: off
Green LED: illuminated
Green LED: 1 brief pulse
Red LED: illuminated +
Red NETS LED: off
Red LED: illuminated +
Red NETS LED: illuminated
Green/Red LEDs:
Alternately blinking
SQR 14.2 Control unit - electromechanical
cables: AUMA article number
A
Colour of wire insula-
tion
Yellow
Orange
White
Blue
Status
Explanation
Not Initialised
No voltage or module in "SETUP" or "NW_INIT"
status
Normal Operation
The module has aborted "NW_INIT" status
Diagnostic Events
Diagnostic events available
Exception Error
Device in "EXCEPTION" status
Fatal Event
Internal device error
Firmware update
Do not cut power supply!
AC 01.2 Intrusive Profinet
Pin
1
2
3
6