Change passwords
7.4.3.

Timeout for incorrect password entry

7.5.

Language in the display

7.5.1.

Language change

SQR 14.2 Control unit - electromechanical
Menu item Service functions M0222 is only visible, if user level Specialist (4) or higher
is selected.
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter Change passwords either:
click via the menu
via direct display: press
-
Display indicates: ▶ Change passwords
-
The user level is indicated in the top row (1
-
For user level 1 (view only), passwords cannot be changed. To change pass-
words, you must change to a higher user level. For this, enter a password via
a parameter.
4.
For a user level between 2 and 6: Press push button
The display indicates the highest user level, e.g.: For user 4
5.
Select user level via push buttons
Display indicates: ▶ Change passwords Password 0***
6.
Enter current password (→ enter password).
Display indicates: ▶ Change passwords Password (new) 0***
7.
Enter new password (→ enter password).
Display indicates: ▶ Change passwords For user 4 (example)
8.
Select next user level via push buttons
via Esc.
A timeout for incorrect password entry is provided with actuator controls.This prevents
unauthorised access by systematic trials. The timeout is active for incorrect entries
via the local controls as well as incorrect entries via our software tools (AUMA CDT,
AUMA Assistant App). After five subsequent incorrect trials, further entry is inhibited
for one minute. Each further incorrect entry doubles the timeout period. An active
timeout is displayed on the screen. An individual timeout is available for each user
level. This means that you may still log on with user level 3 if user level 4 is inhibited.
The incorrect entry counter can be reset in two ways:
1.
Correct password entry with successful access authorisation.
2.
8 hours after the last incorrect entry.
The display language can be selected.
Display M0009
Language M0049
to parameter, or
and enter ID M0229
6), e.g.:
Up ▲ Down ▼ and confirm with
Up ▲ Down ▼ or cancel the process
Operation
Ok.
Ok.
41