CLEARANCES

The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
B36XTCE Clearance Requirements
Clearance:
A: Mantel Height (min.)
B: Sidewall
12" (305mm) one side
C: Ceiling
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
Notes:
C
D
F
|
18
Bellavista® B36XTCE-11 Gas Fireplace
Dimension
21-1/4" (540mm)
Top of Fireplace Opening
Side of Fireplace Opening
only
39" (991mm)
Top of Fireplace Opening
12" (305mm)
29-1/4 " (743mm) from
Top of Fireplace Opening
84" (2134mm)
Wall to Wall (Minimum)
36" (914mm)
Front to Back Wall (Maximum)
0"
No Hearth Required
E
Alcove
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
Measured From:
C
WARNING
Fire hazard is an extreme risk
F
E
Close to Ceiling
Minimum Vent Clearances
to Combustibles
Horizontal Top
2" (51mm)
Horizontal Side
1-1/2 " (38mm)
Horizontal Bottom
1-1/2" (38mm)
Vertical Vent
1-1/2" (38mm)