Masonry Fireplace Clearances; Wood Insert Specifications - Regency Cascades I2500-1 Owners & Installation Manual

Wood fireplace insert
Hide thumbs Also See for Cascades I2500-1:
Table of Contents

Advertisement

installation
|
6

MASONRY FIREPLACE CLEARANCES

The minimum required clearances to combustible materials when installed into a masonry fireplace are listed below.
Unit
Adjacent
Mantle **
Side Wall
(to Top of
I2500-1
(to Side)
A
12"
17-1/4"(438mm)
(305 mm)
f o r
(89mm) mantel
22-1/2"(572mm)
for 12" (305mm)
mantel
Side and Top facing trim is a maximum of 1-1/2" (38mm) thick.
If top/side facing trim protrudes more than 1-1/2"(38 mm) follow mantle (B)** & adjacent side wall (A) for proper clearances.
12
10
8
6
4
24
22
12" (305mm) Mantel
20
3-1/2" (89mm) Mantel
18
16
22-1/2"
14
(572mm)
12
10
17-1/4"
(438mm)
8
6
4
2
0
Top of
Unit
Clearances are critical.
**Mantel can be installed anywhere in shaded area
or higher using the above scale.
Note: Ensure the paint that is used on
the mantel and the facing is "heat
resistant" or the paint may discolour.
WOOD INSERT
SPECIFICATIONS
Your fireplace opening requires the following
minimum sizes:
Height: 21.5" (546 mm)
Width:
25" (635 mm)
Depth:
17" (432 mm)
Two faceplates are available to seal the fireplace
opening:
Standard
40" W x 30" H
48" W x 33" H
1016mm W x 763mm H 1219mm W x 838mm H
6
|
Regency I2500-1 Wood Fireplace Insert
Top
Facing Trim
Unit)
(to Top of Unit)
B
C
16"
3 - 1 / 2 "
(406 mm)
2
Side View
*Floor Protection
Floor thermal insulation/protection with a R value of 2.8 is required if the unit is 0 - 3" (0-76mm)
(measured from the bottom of the appliance).
Thermal floor protection is not required when unit is raised greater than 3" (76mm) (measured
from the bottom of the appliance). However ember protection is still required. Non-combustible
material such as brick, tile, concrete board, etc. or certified to UL-1618 Type 1 or as defined by
local codes. Type 1 Hearth pad extensions typically provide protection from embers only, but
won't provide thermal protection from the heat of the appliance.
Please check to ensure that your floor protection and hearth will meet the standards for clearance
to combustibles. Your hearth extension must be made from a non-combustible material. Extending
16" (406 mm) for US and 18" (457 mm) for Canada—measured from the fuel loading door opening.
F measurement (minimum hearth extension) is taken from the
side of the appliance for both U.S.A/Canada.
Oversize
Side
Minimum
Facing
Hearth
Trim
Extension*
D
E
1/2"(13 mm)
16" (406 mm) USA
to side
18"(457 mm)
surround
Canada
G
Clearance diagram for installations
Minimum
From Base of
Hearth Side
Unit To Top of
Extension*
Unit (Reference
dimension only)
F
G
8"
20"
(203 mm)
(508 mm)
H
F
From Side Of
Unit
(Reference
Dmension Only)
H
31-1/8"
(791 mm)